World Leader in Laboratory Airflow Controls and Monitors.
Call today on +44 (0) 1457 865 635

AFA 1000/BLD

The AFA1000/BLD model is a wall mounting Fresh Air Bleed controller that is suitable for controlling the VAV system duct pressure using a Fresh Air Bleed damper or Fan Inverter drive and includes the following features:-

  • Back lit graphic display with a visual area of 56x27mm showing the duct pressure (Pascals or Ins/wg) with VAV out Bar Graph. In an alarm condition the display will toggle between the duct pressure and alarm condition.
  • Audio Visual Alarm – Audible alarm with Red, Amber and Green LED’s.
  • Password protected pushbutton set up and calibration menus with on screen instructions.
  • 2 Relay Inputs configurable as:- Night Setback /Emergency.
  • 3 Relay outputs activated by any of the 2 inputs or any of the alarm conditions.
  • VAV output to control either VAV damper or Fan Inverter drive.
  • Full PII VAV differential pressure set point control.
  • Com Port – RS485 for connections to a laptop for diagnostics and configuration of the monitor or for connection via a local Modbus RTU network for remote logging with real time graphical displays using the AFA Network software or for direct connection to a BMS system.

Specifications

Specifications


Display range:   0-1000 Pascals (+/- 4.000 Ins/wg)
Alarm range:   0-1000 Pascals (+/- 4.000 Ins/wg)
Control range:   Differential Pressure control 0-1000 Pascals (+/- 4.000 Ins/wg)
Control resolution:  

1 Pascal (0.001 Ins/wg)

Control output:   0-10VDC control output for damper or Inverter drive
Control response:   Less that 1 second
Accuracy:  

Sensor / display resolution 1 Pascal (0.01 Ins/wg) Pressure +/- 1%

Field set-up:  

Zero point calibration (with on-screen instructions)

Alarm delays:   User configurable – 0 to 10secs
Relay input:  

2

Relay output:  

3

Comm. Port:   RS485 – Can be connected via Serial interface to LAN network (Full software available)
Night setback:   Yes
Emergency Input:   Yes
Power Requirement:   Input—240VAC, 50Hz (UK) 230VAC 50Hz (Euro) 120VAC 60Hz (US)
Units:   English and Metric (user selectable)
Display—visual:   VAV output Bar Graph / LEDs: red, alarm; yellow, caution; green, normal / Digital display of pressure reading
Alarm indication:   Red LED & audible alarm (to a certain sound spec)
Horn silence:   Yes (temporary / permanent/automatic depending on type of alarm or external input )
Mounting:   Wall mounting enclosure
Monitor operating temp:  

55-86°F (13-30°C)

Storage temperature:   -40-150°F (-40-65°C)
Agency listings:   CE
Hazardous area:   With Suitable rated Pressure sensor for Gas group llC Temp Class T6 (With Atex certified MTL Zener Barriers).

 

Product Download

Dimensions

Ordering Options


BLD MK2 UK MPC
Model Style Power Supply Comms
BLD MK2 US - 120v 60Hz
Euro - 230v 50Hz
UK - 240v 50Hz
M -RS485
MPC - (Modbus RTU)

 

Power Supply

The AFA1000/BLD Room pressure controller is supplied with PCB terminals for power connections. The mains supply should be fused 3A.

Comms

The AFA1000/BLD can be supplied with configuration software and cable for connections to a laptop for diagnostics and configuration of the monitor or for connection via a local Modbus RTU network for remote logging with real time graphical displays using the AFA Network software or for direct connection to a BMS system. See Modbus RTU Comms on additional features page.

 

Additional Features


The AFA1000/BLD controller range includes the following additional features:-

  • Outputs for 2 x damper actuators, (max 30VA / 30VDC per output).
  • Modbus RTU Coms – For connection to AFA Network or BMS.

The AFA1000/BLD can be supplied with a custom overlay (details on request).

 

Accessories & Airflow Sensor Options


Accessories

 

ANAB Accredited. BSI. UKAS Quality Management 003.

Temperature Electronics Ltd.
Unit 2
Wren Nest Road
Glossop SK13 8HB
UK

T. 01457 865 635
F. 01457 868 843
E. sales@tel-uk.com